Installation Conforme À Ul - Sew Eurodrive MOVIFIT FDC Notice D'exploitation

Table des Matières

Publicité

Installation électrique
5
Consignes d'installation (toutes exécutions)
5.3.11
Installation conforme à UL
Field Wiring Power Terminals
Short Circuit Current Rating
Branch Circuit Protection
Ambient Temperature
Wiring Diagrams
UL-compliant installation
50
Notice d'exploitation – MOVIFIT
REMARQUE
Le chapitre suivant est toujours en anglais, indépendamment de la langue de la pré-
sente documentation et ce en raison des prescriptions UL.
Use 75 °C copper wire only.
®
MOVIFIT
-FDC uses cage clamp terminals.
When installed in combination with listed MOVIGEAR
Suitable for use on a circuit capable of delivering not more than 200,000 rms symme-
trical amperes when protected by 40 A, 600 V non-semiconductor fuses or 500 V mini-
mum 40 A maximum inverse time circuit breakers:
®
MOVIFIT
-FDC, max. voltage is limited to 500 V.
For maximum branch circuit protection see table below.
Series
non-semiconductor fuses
®
MOVIFIT
-
FDC
®
MOVIFIT
-FDC is suitable for an ambient temperature of 40  °C, max. 60  °C with
derated output current. To determine the output current rating at higher than 40°C,
the output current should be derated 3.0 % per °C between 40°C and 60°C.
For wiring diagrams, please refer to the English operating manual "MOVIFIT
FDC" (see http://www.sew-eurodrive.com).
For UL-compliant installation, only the EBOX specified on the ABOX nameplate
may be mounted to the ABOX. The UL certification refers only to the ABOX /
EBOX combination stated on the nameplate.
The standard version of MOVIFIT
short-circuit and ground fault protection for the supply cables to the MOVIGEAR
DRC drive units. The protection device is set to 15 A or 20 A depending on the
type.
®
For MOVIFIT
-FDC variants without integrated short-circuit and ground fault
protection of the supply cables to the MOVIGEAR
ensure this protection by suitable external measures.
The UL certification only applies for the operation on voltage supply systems with vol-
tages to ground of max. 300 V. The UL-certification does not apply for the operation
on voltage supply systems with a non-grounded star point (IT systems).
®
FDC
40 A / 600 V
®
-FDC is equipped with integrated, UL-approved
®
/ DRC drive units:
inverse time circuit breaker
500 V minimum, 40 A maximum
®
/ DRC drive units, you have to
®
-
®
/