HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
2
120 VAC
MECHANICAL
HUMIDIFIER
HUMIDISTAT
YELLOW WIRES
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24V WIRING.
Fig. 5. Typical wiring diagram for humidifier using fan control to
cycle blower motor fan and humidifier simultaneously.
MECHANICAL
HUMIDISTAT
2
HUMIDIFIER
YELLOW WIRES
CURRENT
SENSING
RELAY
1
POWER SUPPLY.
PROVIDE DISCONNECT
MEANS AND OVERLOAD
LO
PROTECTION AS REQUIRED.
C
HI
BLOWER
2
24V WIRING.
MOTOR
Fig. 6. Typical wiring diagram of current sensing relay with
humidifier.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
Template (entire sheet), Top of Humidifier
TO BLOWER
MECHANICAL
MOTOR
1
HUMIDISTAT
IGNITION BOX
SAIL
SWITCH
M12686A
Fig. 7. Typical wiring diagram of sail switch with humidifier.
Plumbing Saddle Valve
Hot or cold water, either hard or softened, can be used in the
humidifier.
120 VAC
1
1. Use the self-piercing saddle valve (included) to tap into the
water supply line at an appropriate location.
CAUTION
Equipment Hazard.
Can cause equipment damage.
• Do not use any line connected to an air conditioner.
IMPORTANT
M12684A
• The saddle valve is not designed to regulate water flow; the
valve is either open or closed.
• To prevent debris from clogging the solenoid in-line filter, be
sure to install the saddle valve handle pointing toward the
ceiling.
2
120 VAC
1
HUMIDIFIER
YELLOW WIRES
1
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
2
24V WIRING.
M12685A
® U.S. Registered Trademark
© 2010 Honeywell International Inc.
69-1175EF—05
K.K. Rev. 02-10
Printed in U.S.A
Template (entire sheet)
NOTE: Lightly clean the copper tubing ends with fine sandpaper
before making any connections.
2. Use 1/4 in. O.D. copper tubing and connect the saddle valve to
the inlet side of the solenoid valve.
a. Place the brass compression nut over the copper tubing.
b. Slide the brass ferrule over the tubing.
NOTE: Do not over-tighten the compression nut. Moderate
tightness prevents leaking.
c. Insert the tubing into the solenoid valve fitting and support
the valve while tightening the compression nut.
NOTE: Slope hose downward for correct drainage.
3. Connect a 1/2 in. hose to the humidifier drain fitting and run it to
a suitable drain.
CHECKOUT
1. Open the saddle valve.
NOTE: The furnace blower must be operating for the
humidifier to work.
2. Set the thermostat setpoint 10°F (6°C) above the room
temperature.
3. Set the humidistat to a high humidity setting, or place the
humidistat in the test position.
4. Observe the water running out of the drain line to be sure the
humidifier is working correctly.
5. Check for leaks.
6. Reset the thermostat and humidistat to comfortable settings.