Installation Instructions; Limits Of Use - Johnson Controls YORK ENJC 09 D-R Instructions D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 20
by johnson controls

Installation Instructions

Inspection
Upon reception, inspect the equipment and
notify both the carrier and the insurance
company, in writing, of any possible damage.
Environmental protection
Eliminate packing in accordance
with the regulations in force on
environmental conservation.
During installation and maintenance, keep
in mind that HFC-410A and oil POE are
used.
Contains greenhouse effect fluorided
gas covered by the Kyoto protocol.
For the type of gas and quantity per system,
see the identification plate. GWP (Global
Warming Potential): 2088.
Safety
Installation and maintenance operations
of this air conditioning system should be
carried out only by qualified and expert
personnel.
Periodical maintenance operations should
be carried out, such as cleaning the coils and
air filters, so as to keep unit performance at
an optimum.
Caution
This unit should be installed and used in
accordance with:
- Low Voltage Electrotechnical
Regulations.
- Safety Regulations for Cooling
Plants and Installations.
- Regulations on Pressure Equipment.
- Basic Construction Standards.
- Technical Construction Standards.
- Local ordinances.
Location (Fig. 1 to 3)
To be installed directly outdoors. Place the
unit on a consistent base and fasten by
means of bolts.

Limits of use

Air intake temperature to outdoor coil DB
Operating cycle
Minimum °C
Cool
Heat
-10
-15
Notes: WB = Wet bulb. DB = Dry bulb.
(1) This equipment can operate at a temperature out of limits for a short period of time, until the occupied space is conditioned.
12
Outdoor units
These units are supplied with an R-410A
refrigerant charge, which is sufficient for an
interconnecting piping length of 5 meters.
Each unit includes a connecting elbow for
the condensed water drain.
Installation
Unit installation comprises:
- Unit mounting.
- Refrigerant tubing connections.
- Condensed water drain connections in
heat pump units.
- Unit wiring.
Clearances, outdoor unit
A minimum clearance is required around
the units for the circulation of air and access
for maintenance servicing, as indicated in
the general dimensions.
Interconnection of the units
When installing Split units, the cooling
circuit should be completely leakproof after
mounting.
This will help to obtain maximum performance
with minimum consumption, and avoid serious
damage to the unit. This is an ecological
precaution as well.
Installation of interconnecting
pipes
The length of the interconnecting tubing of
the units should be as short as possible.
The maximum admissible distances with
regard to the circuit and standard tubing
diameters are indicated on each apparatus
of the corresponding indoor units.
Pipes to be used
Special care should be taken that the tubing
that interconnects the two units is kept
clean and dry, even prior to installation. It is
advisable to take into account the following
recommendations:
- Use copper refrigerant quality tubing
only.
Maximum °C
Cool
Heat
50
24
GB
- Do not work outdoors when raining.
- The ends of the tubing should remain
closed during installation.
- Do not leave dryer filters or the compressor
out in the open air.
- For welding use low melting point rods
with a 5% silver content, minimum.
- When welding and as long as the tubing is
hot, maintain a flow of dry nitrogen so as to
avoid internal rusting and scaling that could
cause contamination and obstructions.
- Do not use strippers on copper-copper
joints.
- Connection between units should be
carried out by means of the flaring
method.
Insulation of refrigerant pipes
To
avoid
temperatures, radiation and condensation,
the pipes should be insulated. Minimum
thickness should be 8 mm.
Emptying and dehydrating
(Fig. 5)
Air does not act as a refrigerant since it
cannot be liquefied by the compressor.
Any air and humidity remaining in the
cooling system has undesirable effects, as
indicated below. Consequently, they should
be eliminated completely.
- High pressure increases.
- Consumed power supply increases.
- Equipment performance decreases.
- Water contained in the air could freeze
and block the capillaries.
- Water can cause corrosion of certain
parts of the circuit, and deterioration of
the compressor.
Process
In each circuit, with the valves closed:
1- Connect a vacuum pump and service
pressure gauges.
2- Carry out a vacuum of up to at least 200
microns.
3- Detect leaks.
Air intake temperature to indoor coil
Operating cycle
Minimum °C
Cool WB
Heat DB
19
20
(1)
the
influence
of
outdoor
Maximum °C
Cool WB
Heat DB
23 (1)
27

Publicité

Table des Matières
loading

Table des Matières