Operation
14
4
13
Hour Meter (if equipped)
The Hour Meter tracks hours of operation for scheduled
maintenance.
The CHG OIL display will illuminate every 100 hours. The
message will flash one hour before and one hour after
each 100 hour interval, providing a two hour window to
perform service.
The SVC display will illuminate every 100 hours. The mes-
sage will flash one hour before and one hour after each
200 hour interval providing a two hour window to perform
service.
When the hour meter is in flash alert mode, the mainte-
nance message will alternate with elapsed time in hours
and tenths. The hours will flash four times, then alternate
with the maintenance message four times until the meter
automatically resets.
100 hours - CHG OIL — Oil Change Interval (Every 100
hrs)
200 hours - SVC — Service Air Filter (Every 200 hrs)
The hour glass icon will flash when the
NOTICE:
engine is running. This signifies the
meter is recording hours of operation.
0000.0
10
10
007652
8
008090

Connection Plugs

120 VAC, 20 Amp, GFCI Duplex Receptacle

This is a 120 Volt outlet protected against overload by a
20 Amp push-to-reset circuit breaker. Use each socket to
power 120 Volt AC, single phase, 60 Hz electrical loads
requiring up to a combined 2400 watts (2.4 kW) or 20
Amps of current. Use only high quality, well-insulated, 3-
wire grounded cord sets rated for 125 Volts at 20 Amps
(or greater).
120/240 VAC, 30 Amp Receptacle
Use a NEMA L14-30 plug with this receptacle (rotate to
lock/unlock). Connect a suitable 4-wire grounded cord
set to the plug and to the desired load. The cord set
should be rated for 250 Volts AC at 30 Amps (or greater).
Use this receptacle to operate 120 Volt AC, 60 Hz, single
phase loads requiring up to 3600 watts (3.6 kW) of power
at 30 Amps or 240 Volt AC, 60 Hz, single phase loads
requiring up to 7200 watts (7.2 kW) of power at 30 Amps.
The outlet is protected by a 30 Amp double-pole circuit
breaker.

Idle Control Switch

When this switch is ON, the engine operates at normal
(high) rpm when there is an electrical load present and
automatically reduces the engine to a lower rpm when a
load is not present. When this switch is OFF the engine
operates at normal (high) rpm.
Ensure this switch is OFF when starting or stopping the
engine, or for use with a transfer switch.
Instruction Manual for Portable Generator