Hazardous Voltage
Will cause death or serious injury
Turn off and lock out all power supplying this device before
working on this device.
Replace all covers and close the enclosure door before
power supplying this device is turned on.
Prepare device for Shield Kit installation.
Step 1 Turn OFF and lock out all power supplying this device before working on this device.
Step 2 Turn OFF Switch.
Step 3 Look at nameplate for amperage of switch, check for 3 – Ø .175" holes in side of the base
plates in locations shown below. If holes are not present, drill, per locations shown below.
Hole locations for 3- Ø.175 holes
Line
Side
Load
Side
30 Amp
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Desenergice totalmente antes de instalar o darle servicio.
Reemplace todas las barreras y cubiertas antes de
energizar el interruptor.
CAUTION
Metal chips may damage switch
mechanism. Cover to prevent metal
chips from dropping into mechanism
when drilling.
Line
Side
Load
Side
60/100 Amp
3 / 6 English
Released Production, 0P v3, Jul 15, 2011
Tension dangereuse.
Danger de mort ou risque de blessures graves.
Couper l'alimentation de l'appareil et barrer avant de
travailler.
Remplacez touts les couverts avant que
l'approvisionnement de pouvoir soit alimenté.
Line
Side
Load
Side
200 Amp
I.L. No. 500551A00