DCLV2 with ELCU-200
The DCLV2 can be used with the ELCU-200 to turn the lights to full ON upon an emergency. The DCLV2 opens the 0-10V circuit at time
of power loss. If the Emergency lighting was in a dimmed state when the normal power was lost, the emergency lighting will be at 100%
versus last dimmed level. The ELCU-200 or some like device needs to be involved in the overall emergency management system to
monitor the loss of normal power so that the 0-10 volt emergency lighting will not only be ON but ON at 100%.
Normal Switched Sense
(Red 18AWG)
Normal Neutral
(White 18AWG)
Normal Power Sense
(Black18AWG)
ELCU-200
Cut jumper loop to use with Normally Closed
test switch, fire alarm panel, security panel, other
White
Neutral
Black
Line
All manuals and user guides at all-guides.com
Emergency Power Out
(Red 12AWG)
Emergency Neutral
0-10VDC Dimming
(White 18AWG)
Ballast Required
Emergency Power In
(Black12AWG)
Emergency Line
Push
to Test
Emergency Neutral
Red
BZ-XXX
Red
POWER PACK
Control
Typical
Common
3 Wire
Occupancy
+24VDC
Sensor
Violet
Emergency
Lighting
Gray
LOAD 1
L
o
a
Switch
d
(optional)
Relais externe 1
Violet
Gray
3
+24VDC
Common
DCLV2
0-10V
0-10V
Control
Ground
Ground