Function and features
• The controller
both in accordance with the AS-i version 2.1), a mini controller and a
fieldbus interface (optional)
• It controls the exchange of data to the sensor/actuator level
• processes the peripheral data in the integrated processor (signal pre-
processing)
• works as stand-alone controller with exchange of data to the PC
(visualisation)
• communicates with the higher control level (in the gateway mode)
Programming interface RS232C
• Baud rate 4800 to 115,200 baud
• Max. distance between controller
• Potential separation from the controller
• Programming cable E70320 for connection to host required
Installation
Fix the controller
is IP20, therefore it should be mounted in a protected location (e.g.
control cabinet).
Ensure a condensation-free environment. Avoid excessive dust,
vibration and shock. The air circulation through the vents must
not be impeded.
Avoid installation in direct vicinity of frequency inverters.
All manuals and user guides at all-guides.com
integrates one or two AS-i masters (AC1303/AC1304,
e
onto a 35 mm rail. The protection rating of the unit
e
and host: 20m
e
power supply
e
9