5-3. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
Input Voltage (V)
Rated Maximum Supply Current I
Maximum Effective Supply Current I
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG (mm
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG (mm
Reference: 2017 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" . See UL 248.
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amps), and UL class "H" ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16) and is based on allowable ampacities of insulated copper conductors having a temperature rating of 167°F (75°C) with not more than
three single current−carrying conductors in a raceway. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table
400.5(A) for flexible cord and cable requirements.

5-4. Extension Cord Data

Input Power
Phase
Input Voltage
120 V
1
OM-272180 Page 14
.
A complete Parts List is available at www.HobartWelders.com
(A)
1max
(A)
1eff
1
2
Time-Delay Fuses
3
Normal Operating Fuses
2
4
)
2
4
)
Hertz
50/60
A 15 or 20 ampere individual branch
circuit protected by time-delay fuses or
Conductor Size
12 AWG
Elec Serv 2017−01
50/60 Hz Single Phase
120
circuit breaker is required.
See Section 5-5.
Max. Cord Length
50 ft (15 m)