1) Check that the mains electrical equipment connected to cubicle
conforms to current electrical standards and regulations and is fitted
with a fully efficient earth connection.
2) Current electrical regulations forbid the installation of any electrical
equipment (e.g. plugs, switches) inside a radius of 60 cm from the
cubicle and at a height of 225 cm.
3) Check that rating of the mains power supply line matches the absorbed
power specified for the cubicle (see Technical specifications).
4) The electrical connection between the cubicle and the mains must be
protected against water spray and must have a protection rating of
IP55 or higher.
5) The electrical equipment upstream from the cubicle must be fitted with
an omnipolare 30 mA switched circuit breaker with a minimum contact
opening of 3 mm, which conforms to current electrical regulations.
6) The manufacturer declines all responsibility for injury or damage
resulting from failure to observe these instructions.
IMPORTANT:
WITH WATER HARDNESS GREATER THAN 14°F (8 D°), INSTALLING THE
LIMESCALE FILTER, CODE R90FLATC01, IS MANDATORY. FAILURE TO INSTALL
THIS FILTER NULLIFIES THE WARRANTY!
7
ENGLISH