Mounting Procedure; Model Selection; Wiring Procedure & Fusing; Terminal Strip Wiring Instructions - DART Controls 125D Manuel D'instructions

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DO NOT MOUNT WHERE AMBIENT TEMPERATURE IS OUTSIDE THE RANGE OF -10
HORSEPOWER
150mA thru 5.5 A
1/50 thru 1/8
1/8 thru 1
NOTE: * With -HS(125D) or suitable external heatsink (where 125D extrusion temperature does not exceed 70° C.), maximum U.L.
for Output Amps can be increased to 10 Amps D.C.
WIRING PROCEDURE & FUSING
1. Size all wires which carry armature or line currents AS SPECIFIED BY NATIONAL, STATE, AND/OR LOCAL CODES. All
other wires may be # 18 AWG or smaller as permitted by local code.
2. Separate control wires from the armature and AC lines when routed in conduit or in wire trays.
3. Fusing - The motor and control are protected against overloads by the current limit circuit and a customer installed fuse in
the AC line. THIS PROTECTION ALREADY MAY BE PROVIDED BY THE CUSTOMER WITH CIRCUIT BREAKERS OR
FUSES IN BOTH MAIN LINES. IF NOT:
FOR 120 VAC INPUT - fuse protection should be added by the customer in AC Line 1 (see following chart)
FOR 240 VAC INPUT - fuse protection should be added by the customer in AC Line 1 and Line 2 (see following chart)
FUSING ADDED BY CUSTOMER (Bussman ABC or Little Fuse 314 Series ceramic fuses)
HORSEPOWER
NOTE: To determine fusing for the 123D-C Series control (24 to 36 VAC input), use 200% of Full Load Current.

TERMINAL STRIP WIRING INSTRUCTIONS

The 125D Series uses an 8 position terminal strip for ease of connection.
P1-1,2
(AC or L) 120 VAC - Connect incoming hot AC or L (black wire) to P1-1 and neutral AC or N (white wire)
(AC or N)
240 VAC - Connect both hot sides (L & N), one to P1-1 and one to P1-2. Connect ground wire
P1-3
(+Arm) Connect to PLUS (+) Armature wire on motor. 0-90 VDC for 120 VAC input or 0-180 VDC for 240
VAC input. See "SPECIFICATIONS" for output rating.
P1-4
(-Arm/-Field) Connects to MINUS (-) Armature wire on motor and, if necessary, connect MINUS (-) Field wire
of SHUNT WOUND MOTOR.

MOUNTING PROCEDURE

1. Eight 3/16" wide slots are provided for control mounting.
2. Control chassis can be used as a template.
3. Use standard hardware to mount.
CAUTION:

MODEL SELECTION

INPUT
OUTPUT
VOLTAGE
VOLTAGE
24 to 36 VAC
0-20 / 0-30 VDC
120/240 VAC
0-90 / 0-180 VDC
120/240 VAC
0-90 / 0-180 VDC
120 VAC INPUT
1/50
1/20
1/8
1/4
1/3
1/2
3/4
1.0
1.5
2.0
to P1-2. Connect ground (green wire) to CHASSIS of control.
to CHASSIS of control.
3
OUTPUT*
AMPS DC
5.5A
1.2A
5.5A
240 VAC INPUT
2 AMP
---------
2 AMP
1 AMP
3 AMP
2 AMP
4 AMP
3 AMP
6 AMP
3 AMP
8 AMP
4 AMP
12 AMP
6 AMP
15 AMP
8 AMP
----------
12 AMP
----------
15 AMP
C (15
F) TO 45
C (115
F)
o
o
o
o
MODEL
NUMBER
123D-C*
125D-12C
125DV-C*
(continued of following page)