IO-Link Data Dictionary
21.10.01.00065/02
Diagnostic Buffer - Details
Data Format of Single Entry (ISDU 132)
Bytes 0...1
Bytes 2...5
Diagnostic-Type (MSB first)
Counter cc1 (MSB first)
Data Format of Diagnostic Buffer (ISDU 131)
Bytes 0...5
Bytes 6...11
Bytes 12...17
Entry 1 (newest)
Entry 2
Entry 3
Encoding of Diagnostic-Type
Diagnostic-Type
Description
Notifications
0x1401
Notification: Device powered on
0x1402
Notification: Diagnostic buffer cleared
0x1403
Notification: Parameters restored to factory defaults
0x1404
Notification: Vacuum sensor calibrated successfully
0x1405
Notification: Manual mode entered
0x0405
Notification: Manual mode exited
0x14AA
Notification: Corrupted entry
Errors
0x1201
Error E01: Internal Error
0x1202
Error E02: Internal Error
0x1203
Error E03: Vacuum sensor calibration failed
0x1207
Error E07 appeared: Primary voltage US too low
0x0207
Error E07 disappeared: Primary voltage US too low
0x1208
Error E08 appeared: IO-Link communication interrupted
J. Schmalz GmbH
...
Bytes 223...228
...
Entry 38 (oldest)
9 of 11
SCPSi series
J. Schmalz GmbH
Aacher Straße 29, D 72293 Glatten
Tel.: +49(0)7443/2403-0
Fax: +49(0)7443/2403-259
info@schmalz.de
Remark
Counter value cc1 of when the entry was recorded
Remark
Buffer of 38 entries (newest to oldest) with encoding as in ISDU 131
Remark
Single entry was written incorrectly - do not evaluate
Remains until next power-on
Remains until next power-on
29.08.2014
SCPSi Data Dictionary