Unit description & Main components
Medium temperature condensing unit is equipped with a BLDC compressors a Flash valve and an HPV
valve.
The compressor is taking in charge the evaporation pressure control for the medium temperature
refrigerated devices.
The Flash valve is controlling the pressure inside the receiver. The HPV valve is controlling the Gas Cooler
pressure.
The system operates at the following pressures:
MT Compressor discharge pressure (PGC): operating between 45-105 bar
MT Compressor suction pressure: operating between 25 - 30 bar
Receiver pressure: operating between 40 – 50 bar
Compressor modulation range: 25 – 100 rps
Liquid filter
dryer
Flash valve
Water
Outlet
Water
Inlet
Speed driver
MT compressor
Figure 1: UMT/WG T with 2 x 2,4 lt Liquid Receiver
Pag. 6-EN
3 Way Valve
Receiver
OEM Manual – CUBO
PHE Gas Cooler
HPV valve
AQUA
2
NRV
Valve
Electrical
board
UMT/WG T MT Rev3.0 – 08/10/2021
MT
compressor