OEM Manual – CUBO
Mask
Topic
Description
index
Gas cooler pressure probe broken
or disconnected.
ALA02
Gas cooler pressure probe broken,
disconnected or not properly
configured
External temperature probe broken
or disconnected.
ALA03
External temperature probe could
be broken, disconnected or not
properly configured
Suction pressure probe broken or
disconnected.
ALA24
Suction pressure probe broken,
disconnected or not properly
configured
Suction temperature probe broken
or disconnected.
ALA25
Suction temperature probe broken,
disconnected or not properly
configured
gas cooler out temp.probe broken.
Gas Cooler outlet temperature
ALA43
probe broken, disconnected or not
properly configured
Receiver pressure probe broken,
ALA44
disconnected or not properly
configured
Common high condensing pressure
switch alarm.
High Pressure pressure switch (for
ALB02
Parallel/MT compressor). It is active
when Gas Cooler pressure is higher
than the pressure switch threshold
Low condensing pressure alarm.
ALB03
Gas Cooler pressure is lower than
the threshold set in the mask De07
High condensing pressure alarm.
ALB04
Gas Cooler pressure is higher than
the threshold set in the mask De06
High suction pressure.
ALB15
Suction pressure higher than alarm
threshold (settable by mask Cae24)
Low suction pressure.
Suction pressure (read by probe)
ALB16
lower than the alarm threshold
(settable by mask Cae26)
UMT/WG T MT Rev3.0 – 08/10/2021
AQUA
2
Serious
alarm
x
x
x
x
x
x
Normal
Action
alarm
No action on the regulation
The opening of HPV valve
x
will be fixed at a safety
value settable in mask
Fhb13
All Functions managed by
this probe will be disabled:
- Floating Condensing
setpoint
- auto-switch of regulation
x
on T_ext in case of
T_outlet_GC is fault (mask
Dag14)
- speed up opening of gas
cooler 3way-valve according
to T_ext (mask Dag13)
Shut off of LT/MT
compressor (according to
the setting made on mask
Cag03)
x
No action on the regulation
Shut off Gas Cooler 3Way
Valve
No action on the regulation
RPRV will open at a safety
position(settable by Fhb26)
Shut off Parallel/MT
compressor
Shut off the Gas Cooler
3Way-Valve
Forces Gas Cooler 3Way-
Valve at 100%
x
No action
Shut off LT/MT compressor
x
(settable by mask Cae27)
EN
Delay
Reset
No delay
Automatic
No delay
Automatic
No delay
Automatic
No delay
Automatic
No delay
Automatic
No delay
Automatic
Settable
Automatic
(by mask
/ manual
Hc01)
Settable
(by mask
Automatic
De03)
Settable
(by mask
Automatic
De01)
Settable
(by mask
Automatic
Cae25)
Settable
(by mask
Automatic
Cae27)
Pag. 27-EN