Alarm pull station - PH1
English
Proof Testing
Proof testing is carried out by using the 'LIFT' and 'PULL '
handles to activate the safety function as described above
and ensuring that the switch has been actuated. It should
also be checked that the switch has been returned to its
normal operating position after being manually reset as
described above.
Conditions of Safe Use
The following conditions apply to the installation,
operation and maintenance of the PH1 call point. Failure
to observe these may compromise the safety integrity of
the assessed equipment.
1.
The user shall comply with the requirement
given in this Safety Manual and Technical Manual
regarding all relevant functional safety aspects such as
application of use, installation, operation, maintenance,
proof tests, maximum ratings, environmental conditions,
repair, etc.
6
AlArm pull stAtion - pH1 TM230 Issue F July 2019 www.eaton.com
2.
Selection of this equipment for use in safety
functions and the installation, configuration, overall
validation, maintenance and repair shall only be
carried out by competent personnel, observing all the
manufacturer's conditions and recommendations in the
user documentation
3.
All information associated with any field
failures of this product should be collected under a
dependability management process (e.g. IEC 60300-3-
2) and reported to the manufacturer.
4.
The unit should be tested at regular intervals to
identify any malfunctions; in accordance with this safety
manual