Multi Variable Air Conditioners Cassette Type Indoor Unit
①-Drainage pipes assembled by T-shaped joints
(7) The horizontal pipe can't be connected to vertical pipe in the same level; please select the
connection way as shown in following fig.
NO1: Three-way connection of drainage pipe joints (Fig 4.3.2.2)
NO2: Connection of downspout elbow (Fig 4.3.2.3)
NO3: Inserting horizontal pipe connection (Fig 4.3.2.4)
Fig 4.3.2.2
(8) Drainage pipes should have a downward slope of at least 1%~2%, in order to prevent
pipes from sagging; install hanger bracket at intervals of 1000~1500mm.
(9) The installation height of raising pipe for drainage should be lower than 850mm. The
gradient from raising pipe towards drainage direction should be at least 1%~2%. If the
raising pipe is vertical with the unit, the raising height should be less than 800mm., as
shown in Fig 4.3.2.6.
model
GMV-ND22T/B-T
GMV-ND28T/B-T
GMV-ND36T/B-T
GMV-ND45T/B-T
GMV-ND50T/B-T
GMV-ND56T/B-T
(10) If the raising pipe is vertical with the unit, the distance between raising pipe and unit
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Fig 4.3.2.3
Fig 4.3.4
A(mm)
170
Fig 4.3.6
11
Fig 4.3.2.4
B(mm)
830