Programming a new Stow position with a "6-Wire" system
When using a Six Wire Controller (Dip Switch 1 is UP), it will be necessary to temporarily borrow a switch function from the toggle
switch operator station or controller . For Learning a new Stow position, we will
temporarily use the FOG switch, or button, as a STOW switch.
1 - Turn power OFF .
2 - Disconnect the "Fog" wire (usually brown or tan) from TB1, terminal 1(or terminal 15 - usually best to use the
operator station that is closest to Monitor), and connect it to TB1, terminal 21 (Stow) .
3 - Make sure that the DIP switches in the Logic Box are set as follows:
DIP Switch 1 = DOWN (Down - towards printed circuit board, "closed")
DIP Switch 2 = DOWN (Down - towards printed circuit board, "closed")
DIP Switch 7 = UP (Up - away from printed circuit board, "open")
DIP Switch 8 = UP (Up - away from printed circuit board, "open")
4 - Turn power ON
Make sure that the truck engine is running while going through the LEARN mode .
Truck voltage should be at normal running level .
5 - Momentarily press either one of the elevation or rotation switches to make sure that the monitor is in the
Deployed mode. LEDs inside the logic box should be ON solid. The unit will not enter the Learn mode for a
new stow position if it is not deployed, or if LEDs are flashing.
6 - Press and hold the FOG switch or button. The monitor will stow into the default stowed position. If at any
point you release the FOG switch, you must start over - go back to step 5.
Monitor should first move Left or Right looking for center of travel. (Magnet closes Horizontal position reed
switch at center of horizontal travel) IF it does not find the magnet / reed switch, it may reverse direction a
couple of times . LEDs inside Logic box will blink out code 3 if horizontal position magnet is not found at this time .
Monitor should then move up or down looking for Elevation magnet / reed switch activation, "telling" it where
it is at during elevation. (Should stop at factory default stow position for elevation) IF it does not find the
magnet / reed switch, it may reverse direction a couple of times. LEDs inside Logic box will blink out code 3
if the Elevation reed switch is not found at this time .
If the monitor times out, or an E-Stop condition occurs, then LEDs inside Logic box will blink out code 3.
Under normal conditions, the LEDs inside Logic box should be blinking out code 2 during stow operation.
7 - When the monitor comes to a stop, continue holding the FOG switch and operate the Raise or Lower
switches to the desired elevation position, then operate the Left or Right switch to the desired rotation
position .
8 - Release the FOG switch. This will be the new Stowed position, LEDs should stop flashing and turn off.
Note: There is no Learn mode for the Deploy Function. See DIP switch numbers 3 and 4.
9 - Set DIP Switch 8 = DOWN (Down - towards printed circuit board, "closed") to lock the LEARN Mode.
10 - Set DIP Switch 1 = UP (Up - away from printed circuit board, "open") to re-enable "6-Wire" operation.
11 - Turn power OFF .
12 - Disconnect the "Fog" wire, from TB1, terminal 21, and re-connect it where it was originally
(TB1, terminal 1 or 15). Unit should now be wired as it was before step number 2.
13 - Turn power back ON, and test monitor functions .