Notes:
Some applications use DIP Switch 6 on the printed circuit board.
Normally, DIP switch 6 is set DOWN (Down - towards printed circuit board, "closed"). During stow, the monitor will move Left/Right,
then Up/Down until it finds the default home position. Then it will move Up/Down, and Left/Right until it finds the Learned
Stowed position .
If DIP Switch 6 is set UP (Up - away from printed circuit board, "open"), During stow, the monitor will move Left/Right, then Up/Down
until it finds the default home position. Then it will move Left/Right, and Up/Down until it finds the Learned Stowed position. If the
Learned Stowed position is set too high, the monitor may only go to the Learned position for rotation (Left/Right)
This was done for certain applications where the mounting and / or the weight of the nozzle was an issue .
Pattern (Fog / Stream) does not have a "Learned" stow position. You can, however set DIP switch 5 for one of two options:
DIP Switch 5 = UP (Up - away from printed circuit board, "open") Returns the nozzle to straight stream during the Stow sequence.
DIP Switch 5 = DOWN (Down - towards printed circuit board, "closed") Leaves the nozzle pattern set where last used
(factory default setting).
With DIP switch 7 in the DOWN position (Down - towards printed circuit board, "closed"), the monitor will stow in the default posi-
tion, and both reed switches should be closed (reed switches and magnets are lined up, facing each other) . TB3, terminals 26 and 27
should have 7 to 8 volts with respect to ground .