STEP 5 Remove the cable grip nut from the plastic bag and put it on the other end of the cable with the threads facing
out . Remove 6 inches of the outer cover and strip back
STEP 6 Remove the 6 logic box cover screws and set the logic box cover aside . Thread the 7 wires through the upper or
lower control hole in the logic box (see component layout, Figure 5). Thread the cable grip washer and cable
grip nutwith the threads facing the box on the cable. Pull enough cable through the cable grip to ensure a good fit.
Tighten the cable grip nut and attach the individual wires to the proper terminals (see wiring diagram Figure 6) .
Reattach the logic box cover and secure with the 6 screws .
NOTE: The lower control and upper control wires must be attached to the correct terminals for the lower control
to over ride the upper control . The one attached to the Master terminal will have the overriding capabilities .
Adjust the DIP switch settings as needed. (Refer to the description below.)
B. DIP SWITCH SETTINGS
The DIP switches are located in the logic box on the circuit board.
The switches are factory set at:
1
UP
DOWN
Switch 1 - Allows the ability to use a 6-wire controller for the Stow controller instead of 10- wire.
UP - Enables the 6-wire Stow controller
DOWN - Disable the 6-wire Stow controller
Switch 2 - Allows the Stow and Deploy switch to be a momentary or a maintain switch.
UP - Requires JOG (maintain) to Stow or Deploy (No Learn mode if DIP 2 is ON)
DOWN - Momentary switch to start the Stow or Deploy sequence (factory set)
Switch 3 - Lowers the monitor during the Deploy sequence for 2.5 seconds.
UP - Deploys for 2.5 seconds (factory set)
DOWN - Will not Deploy the 2.5 seconds
Switch 4 - Lowers the monitor during the Deploy sequence for 3.75 seconds.
UP - Deploys for 3.75 seconds
DOWN - Will not Deploy 3.75 seconds (factory set)
Note:
If Switch 3 and 4 are both ON the monitor will lower for 5 seconds during the Deploy sequence.
Switch 5 -
Allows the nozzle to return to straight stream during the Stow sequence .
UP - Returns the nozzle to straight stream during the Stow sequence
DOWN - Leaves nozzle pattern set where last used (factory set)
Switch 6 -
Stew Sequence. (See Notes on page 9, put definition here)
Switch 7 -
Allows the user to choose between the Learned positions or the Default positions .
UP - Stow at the Learned position (factory set)
DOWN - Stow in the default position only
Switch 8 -
Allows the user to turn the Learn mode ON or OFF
UP - Enables Learn mode programming (factory set)
DOWN - Disable the Learn mode, the user cannot reprogram a new setting
Notes: UP=Away from the bound, towards the "OPEN" position.
DOWN=Pushed DOWN towards the board.
Function is active when DIP Switch is in the "UP" position.
2
3
4
5
3
/
inch from each of the 7 wires .