Product Description
The TIF IR-1A uses infrared optics to create a refrigerant leak detector that
combines sensitivity, speed, battery life, portability and ease of use. This
unit will detect leaks as small as 3 g/yr, and exceeds EN 14624.
The TIF IR-1A comes with a wall charger for its compact lithium-ion battery
- which can power the leak detector for up to eight hours of continuous
operation before needing to recharge. A choice of three sensitivity set-
tings keeps false alarms to a minimum while allowing detection of even the
smallest leak in a refrigerant contaminated environment. A 30 seconds self-
calibration test occurs whenever the unit is powered on to ensure optimal
performance. A built-in replaceable filter blocks moisture and particulates,
preventing damage to the sensor.
Specifications
Sensing element
Refrigerants
Sensitivity levels
Response time
Battery life
Auto off
Battery
Low battery LED
Charge time
Operating environment
Storage environment
For 80 % battery recovery
Accessories included
enhanced infrared photo optics
HFC, CFC, HCFC, HFO1234yf and blends
HIGH: <3 g/yr and higher
MED: <7 g/yr and higher
LOW: <14 g/yr and higher
Exceeds EN 14624 and SAE J2791 standards.
less than one second
up to eight hours of continuous use before recharging
10 minutes of inactivity
3.7 V DC, 1880 mAH rechargeable, lithium-ion battery
(TIF IR-9)
illuminates when one hour of battery life remains
less than 4 hours @ 500 mA
0 °C (32 °F) to 50 °C (122 °F) at <75 % RH
<80 % RH for detector and battery
-20 °C (-4 °F) to 60 °C (140 °F) less than one month
-20 °C (-4 °F) to 45 °C (113 °F) less than three month
-20 °C (-4 °F) to 20 °C (68 °F) less than one year
wall charger, storage case, battery (installed), replacement
filters & O-rings and operator's manual