Configuration using Switches

Adjust the DIP and rotary switches according to the table on the
housing.
Sensitivity:
Use DIP1 to DIP3 to set the number to the left of the decimal point for
the input sensitivity (mV/V).
Use the "Sensitivity" rotary switches (S) to set the numbers to the right
of the decimal point (x.00 ... x.99).
Range
DIP S1
1 2 3
0+S/100
1+S/100
x
2+S/100
x
3+S/100
x x
±(0+s/100)
x
±(1+s/100)
x
x
±(2+s/100)
x x
±(3+s/100)
x x x
Minimimum input range
Within these ranges the exact value is specified by
the rotary switches ("S").
38
Sensitivity
(rotary switches)
Zero
(rotary switches)
DIP S1
DIP 1...3: Sensitivity range
DIP 4...6: Zero range
DIP 7, 8: Output signal selection
-3.99
-2.99
-1.99
-0.99
0
0.99
1.99
2.99
3.99
[mV/V]