General Description; Installing The Product; Mechanical Installation; Outdoor Installation - Grundfos CRE Serie Notice D'installation Et De Fonctionnement

Masquer les pouces Voir aussi pour CRE Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2.3 General description

Grundfos E-pumps have standard motors with integrated
frequency converter. The pumps are for single-phase or three-
phase power supply connection.
2.3.1 Pumps without factory-fitted sensor
The pumps have a built-in PI controller and can be set up for an
external sensor enabling control of the following parameters:
pressure
differential pressure
temperature
differential temperature
flow rate
liquid level in a tank.
From factory, the pumps have been set to control mode
uncontrolled. The PI controller can be activated by means of
R100.
2.3.2 Pumps with pressure sensor
The pumps have a built-in PI controller and are set up with a
pressure sensor enabling control of the pump discharge
pressure.
The pumps are set to control mode controlled. The pumps are
typically used to hold a constant pressure in variable-demand
systems.
2.3.3 Settings
The description of settings apply both to pumps without factory-
fitted sensor and to pumps with a factory-fitted pressure sensor.
Setpoint
The desired setpoint can be set in three different ways:
directly on the pump control panel
via an input for external setpoint signal
by means of Grundfos wireless remote control R100.
Other settings
All other settings can only be made by means of the R100.
Important parameters such as actual value of control parameter,
power consumption, etc. can be read via the R100.
If special or customized settings are required, use Grundfos PC
Tool E-products. Contact your local Grundfos company for more
information.
6

3. Installing the product

3.1 Mechanical installation

The pump must be secured to a solid foundation by means of
bolts through the holes in the flange or baseplate.
In order to retain the UL/cUL approval, follow the
additional installation procedures found in the
Appendix.
3.1.1 Motor cooling
To ensure sufficient cooling of motor and electronics, observe the
following requirements:
Make sure that sufficient cooling air is available.
Keep the temperature of the cooling air below 104 °F (40 °C).
Keep cooling fins and fan blades clean.

3.2 Outdoor installation

When installed outdoors, the pump must be provided with a
suitable cover to avoid condensation on the electronic
components. See fig. 1.
Examples of covers
Fig. 1
Remove the drain plug pointing downwards in order to avoid
moisture and water build-up inside the motor.
Vertically mounted pumps are IP55 after removal of the drain
plug. Horizontally mounted pumps change enclosure class to
IP54.
In order to retain the UL mark, additional
requirements apply to the equipment. See Appendix.

3.3 Electrical connection

For description of how to connect E-pumps electrically, see the
following pages:
3.4 Three-phase pumps, 20-30 hp, page 7.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Crie serieCrne serieSpke serieCrke serieMtre serie

Table des Matières