5.2 Connection diagram

Supply connection
Fig. 6
Wiring diagram
WARNING!
Wires connected to
– supply terminals,
– outputs NC, NO, C and
– start/stop input
must be separated from each other
and from the supply by reinforced
insulation.
All wires connected to a terminal
block must be tied up at the
terminals.
Concerning demands on signal wires and signal
transmitters, see section 11. Technical data.
A connection example can be found on page 49.
Signal output
NC NO C
L
N
NC NO C
Start/stop input
1
2
3
Note:
If no external on/off switch is connected, the
connection across terminals STOP and
be maintained.
All cables used must be heat-resistant up to
+185 °F (+85 °C).
All cables used must be installed in accordance
with NEC or applicable local codes and
regulations.
If a GENI module is fitted, the screen must be
connected to
8
7
S
T
O
P
. See page 50.