Frequency selector
The device has three frequency settings: medium, high and low.
If you are using an installation with a double loop you should use different frequencies for the two loops.
Selecting a higher frequency will increase the sensitivity.
Dip-switch settings
The appliance functions can be set using the block of four dip-switches (numbered from 1 to 4) on the
front of the device. Using dip 1 the device can be set up to work in two different ways: "normal passage
mode" and "rapid passage mode".
dip 1 dip 2
ON
OFF Rapid passage mode
ON
ON Rapid passage + device reset
OFF
OFF Normal passage mode
OFF
ON Normal passage + device reset
Notes:
- Rapid passage mode will reduce the four sensitivity
levels. Dip 2 will set up a control mode that will force
automatic calibration after 10 minutes of continuous
detection
Detection mode
dip 3 dip 4
OFF OFF Minimum sensitivity
ON
OFF Sensitivity setting 1
OFF
ON Sensitivity setting 2
ON
ON Maximum sensitivity
Notes:
- Rapid passage mode will reduce the four sensitivity
levels.