Options:

Alarm contact

A contact with no potential (0,5A - 60V) is
available (12). It warns the user (alarm or control
system) when the inverter has been stopped
due to a failure or is out of use. It is closed when
the inverter is working.

Solar charge controller

This controller has been designed to charge the
batteries with solar installation only. The
maximum no load tension of the solar
installation should be of 23V for the 12V
applications and of 46V for the 24V applications.
The max. DC current is 16A and should never
be exceeded (20A / 1min.). The mode of
adjustment is of the I/U + "floating" type and
assures optimal charging conditions for the life
of the battery.
LED " Charging " (11) :
It is illuminated when the solar module provides
current to charge or maintain the battery.

LED " Bat. 100% " (10) :

It is illuminated when the battery has reached its
max. tension (14,4V or 28,8V). It goes off when
the tension is above 13V (26V).
I declare under that products mentioned on page 11 of this manual are in conformity with the following
standards or standardisation documents :
EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022,
EN 61000-3-2, Dir. 89/336/EEC, LVD 73/23/EEC
th
Sion : June 19
, 1999
User manual
Charging diagram

CE- declaration of conformity

SI V3.0 E

Maintenance

The SI inverters do not need any special
maintenance. The casing may be cleaned with a
damp cloth (not wet).
In the case of malfunction, the inverter should
be sent to the salesperson for control.

Legislation

In all cases the assembly and installation must
be done by qualified technicians, observing the
national requirements and rules stipulated. You
will find complete information about this in the
relevant institutions.

Limitation of liability

Steca cannot control the installation, use and
maintenance of the inverter. Thus, we are not
responsible for damages, costs or losses
resulting from an installation which is not in
accordance with the regulations or
inappropriate use or maintenance.
The customer is always responsible for
the use of the inverters Steca
This device has not been designed and
is not warranted for use in life support
apparatus or any other critical apparatus
with potential risks of serious harm to
people or to the environment.
We do not accept any responsibility for any
violation of patent rights or other third person
rights resulting from the use of the inverter.
Steca reserves the right to modify their products
without previous notice.
Roland Studer
Studer Innotec
6