Setup Functions - Honeywell LUTRON TouchPRO Wireless Guide D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installer setup

Setup functions

0170
System type
0173
Heat pump type
0180
Fan control
(heating)
0190
Changeover valve
(O/B terminal)
0200
Auxiliary Heat
0210
External Fossil Fuel
Kit
0220
1st Stage Cool/
Compressor cycle rate
0230
2nd Stage Cool/
Compressor cycle rate
0240
First stage heat
cycle rate (CPH=
cycles per hour)
0250
Second stage heat
cycle rate (CPH)
0260
Third stage heat cycle
rate (CPH)
0280
Backlight
P/N 041-338 Rev. C
Settings & Options
1
1 heat/1 cool conventional
2
1 heat/1 cool heat pump (no aux. heat)
3
Heat only (2-wire systems)
4
Heat only with fan
5
Hot water Series 20 system (power to open & close zone
valves/normally open zone valves)
6
Cool only
7
2 heat/1 cool heat pump (with aux. heat)
8
2 heat/2 cool multistage conventional
9
2 heat/1 cool multistage conventional
10 1 heat/2 cool multistage conventional
11 2 heat/2 cool heat pump (no aux. heat)
12 3 heat/2 cool heat pump (with aux. heat)
0
Air to air heat pump
1
Geothermal heat pump
0
Gas/Oil heat (equipment controls heating fan)
1
Electric furnace (thermostat controls heating fan)
0
O/B terminal controls valve in cooling
1
O/B terminal controls valve in heating
0
Electric backup heat
1
Fossil fuel backup heat
0
None
1
Yes
3
Recommended for most compressors
[other options: 1, 2, 4, 5, or 6 CPH]
3
Recommended for most compressors
[other options: 1, 2, 4, 5, or 6 CPH]
5 Gas or oil furnaces of less than 90% efficiency
1
Steam or gravity systems
3 Hot water systems & furnaces of 90%+ efficiency
9
Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
5 Gas or oil furnaces of less than 90% efficiency
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
9
Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
9
Electric auxilliary heat
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
5
Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0
Backlight ON for approx. 45 seconds after keypress
1
Backlight always on low intensity, full bright after keypress
7
TouchPRO Wireless
(factory default in bold)
Continued on next page
®
69-2655EFS—05

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Lr-hwlv-hvacLutron lr-hwlv-hvac touchpro wireless

Table des Matières