N.C. safety input. When it is activated in the closing phase it causes the automation to reopen. If it is enabled also in the ope-
ning phase with dip switch 5, it temporarily stops the automation for the time for which it is engaged.
AP.PED
Pedestrian start N.O. input. Allows 10 sec partial opening according to the logic programmed with the dip switches 1-2.
If the pedestrian start control is kept active with the gate closed, there is partial opening, with timer-type operation, and
when it is freed after a pause the gate is closed (dip 1 - 2 ON).
LIMIT SWITCH INPUT
N.C. inputs.
If the direction of rotation is reversed, reverse FCA/FCC.
Dip switches 1 and 2: Select the functioning logic
Off-Off: Dead-man logic
The automation works for held controls.
The start control opens once and closes once.
Regulations prohibit controls via radio with dead-man logic.
Off-On: Semiautomatic logic.
The automation works for pulse controls without automatic reclosing.
So at the end of opening, in both the normal and pedestrian cycle, to control closure it is necessary to use respectively the start or
pedestrian start.
On-Off: Automatic logic type 1.
The automation works with pulses.
In the normal cycle, after the opening phase, automatic closing is activated after the time set on trimmer P2.
In the partial (pedestrian) cycle, the logic is semiautomatic so, at the end of opening, a pulse on the start ped.
On-On: Automatic logic type 2.
The automation works with pulses. In the normal cycle, at the end of the opening phase, automatic closing is activated after the time
set on trimmer P2.
In the partial (pedestrian) cycle, the logic is automatic with a fixed pause time of 10 sec.
- The START control always takes priority over the partial opening cycle with full gate opening.
- If the automation is in a state of black-out on the opening limit switch (FCA), if the logic is set in automatic mode, when power is
restored the gate will close after 3 sec.
Dip switch 3 and 4: Select the response of the logic to the sequence of start controls.
Off-Off: Step-by-step type 1: open-stop-close-stop-open-stop-close
Off-On: Step-by-step type 2: open-stop-close-open-stop-close-open
On-Off: Condominium type 1: control for opening only, on pause a start closes and on closure it reopens.
On-On: Condominium type 2: control for opening only, on pause the start is not considered and on closure it reopens.
Dip 5 Off: Photocells active only on closing: if obscured they reverse the direction.
Dip 5 On: Photocells active on both closing and opening: if the photocells are obscured in either the closing or opening phase, the
automation stops until they are freed to then open.
Dip 6 Off: Safety edge with NC contact.
Dip 6 On: Safety edge with 8,2kΩ resistive contact
Dip 8 Off: Electric braking at limit switch off.
Dip 8 On: Electric braking at limit switch on.
P1 "TORQUE": Sets the useful torque to move the gate after starting for 1,5 sec. at full power.
(Adjustable voltage from 120 to 230V).
P2 "T.PAUSE": Sets the pause time from 2 to 120 sec.
Operation time is set at 90 secs (working manoeuvre). The motor stops after this time.

5.3 J4 TERMINAL BLOCK SAFETY EDGE - ANTENNA

SAFETY EDGE INPUT
Trough Dip Switch 6 is possible to select the activation of the safety edge both in N.C. contact and/or
resistive contact 8,2kΩ

6. DIP-SWITCH CONFIGURATION

7. TRIMMER ADJUSTMENT

Dip 7 Off: Pre-flashing off.
Dip 7 On: Pre-flashing of 2 sec. on.
- 11 -