In order to reach the level of safety required by current regulations, read the following prescriptions carefully.
1) Make all the connections in the terminal block after carefully reading the instructions given in this manual and observing the general
rules and technical standards governing electrical systems.
2) Upstream from the installation, fit an omnipole miniature circuit breaker with a contact gap of at least 3 mm.
3) If there isn't one already, install a residual current device with a threshold of 30 mA.
4) Check the effectiveness of the grounding system and connect to it all the parts of the automation fitted with a terminal or grounding
cable.
5) Fit at least one external warning device, such as a traffic light or flashing light, along with a warning or danger sign.
6) Fit all the safety devices required by the type of installation, taking into consideration the risks it can cause.
7) Separate the power lines (min. sect. 1.5 mm
8) Fit jumpers in the N.C. inputs not used.
9) Set in series any contacts to be connected in series with the same N.C. input.
10) Set in parallel the inputs connected to the same N.O. input.

5. INPUT AND OUTPUT FUNCTIONALITY AND CONNECTIONS

SMART-800
L N E
J1
LAMP
SL-R-AI
N
J2
COM
24Vac
OUT 24V
24Vac output to power safety and control accessories such as photoelectric cells or radio receivers.
SCA
Passageway open indicator light. With four different indicators it shows the automation status:
Slow blinking:
SCA
COM
Fast blinking:
Steady light:
Light off:
Double Flashing: safety edge squeezed
START
N.O. input used to control the automation according to the programmed logic with the dip switches 1, 2, 3, 4
If the start control is kept active with the gate closed, there is total opening, with timer-type operation, and when it is freed
after the pause time set on trimmer P2, the gate is closed.
STOP
N.C. safety input. When it is activated it stops the automation immediately and a subsequent start always causes a
reopening. During the pause time (trimmer P2) a stop control eliminates automatic reclosure, leaving the gate open waiting
for commands.

4. INSTALLATION SAFETY

) from the low-voltage signal lines (min. sect. 0,5 mm
2

5.1 J1 - J2 POWER TERMINAL BLOCK

LINE
230V
230V 50Hz power supply with mov internal protection and 6,3A fuse (5x20).
Connect the phase and neutral as shown on the screen printing. Use a cable type H07RN-F 2x1.5+E min.
Connect the yellow/green wire of the power supply mains to the earth terminal of the appliance.
FLASHING LIGHT: YELLOW at 230V 40W max.
SWITCH THE MOTOR ROTATION
5.2 J3 LOW VOLTAGE INPUT/OUTPUT TERMINAL BOARD
opening phase
closing phase
gate open or even stopped with partial opening
gate closed
- 10 -