Tone Setting
Alarm
Tone Type
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Tone Description /Application
970Hz
800Hz/970Hz @ 2Hz
800Hz – 970Hz @ 1Hz
970Hz 1s OFF/1s ON
970Hz, 0.5s/ 630Hz, 0.5s
554Hz, 0.1s/ 440Hz, 0.4s (AFNOR NF S 2 001)
500 – 1200Hz, 3.5s/ 0.5s OFF
(NEN 2575:2000 Dutch Slow Whoop)
420Hz 0.625s ON/0.625s OFF
(Australia AS1670 Alert tone)
500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF
(AS1670 Evacuation)
550Hz/440Hz @ 0.5Hz
970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201)
2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201)
1200Hz – 500Hz @ 1Hz (DIN 33 404)
400Hz
550Hz, 0.7s/1000Hz, 0.33s
1500Hz – 2700Hz @ 3Hz
750Hz
2400Hz
660Hz
660Hz 1.8s ON/1.8s OFF
660Hz 0.15s ON/0.15s OFF
510Hz, 0.25s/ 610Hz, 0.25s
800/1000Hz 0.5s each (1Hz)
250Hz – 1200Hz @ 12Hz
500Hz – 1200Hz @ 0.33Hz.
2400Hz – 2900Hz @ 9Hz
2400Hz – 2900Hz @ 3Hz
800Hz – 970Hz @ 100Hz
800Hz – 970Hz @ 9Hz
800Hz – 970Hz @ 3Hz
800Hz, 0.25s ON/1s OFF
500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)
Alarm
Dip Switch
2
ON
18
1
2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
4
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
9
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
19
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
18
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
18
1 2 3 4 5 6
ON
19
1 2 3 4 5 6
ON
19
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
18
1 2 3 4 5 6
ON
18
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
1
1 2 3 4 5 6
ON
8
1 2 3 4 5 6
Alarm
Max.
3
dBA@1m
4
97
4
97
4
97
4
97
4
97
4
96
4
97
4
96
4
94
4
97
4
97
4
91
4
94
4
96
4
97
4
93
4
90
4
91
4
86
4
86
4
85
4
96
4
97
4
92
4
97
4
89
4
91
4
91
4
94
4
95
4
97
4
97