HYDRAULIC CIRCUIT
2
1
4
2
8
3
8,5
40
60
60
¾" M
¾" M
In presence of water with max hardness 25 °Fr, is prescribed an appropriate
treatment of the heating water, in order to avoid limescale problems and also an
expansion tank.
It should be noted that even a small quantity of limescale, could reduce the
performances of the domestic side.
The materials of construction are in compliance with the Directive 98/83 EC.
Despite the fittings are mounted at the factory, it is advisable to monitor all screw
connections. Equally important is to do a pressure test during the operation.
Exceeding above listed limits may cause damages to module and impair warranty
terms consequently
9
8
2
5
10
6
2
10 Bar
7
SECTION 3: DIMENSIONS AND CONNECTIONS
340
60
60
60
¾" M
¾" M
¾" M
!
IMPORTANT
Assembling instructions and maintenance
1 Heat meter
2 Ball valve
3 Pump
4 Thermostatic valve
5 Heat exchanger
6 Safety valve
7 Sensor pocket for thermostatic valve
8 Check valve
9 Circulation valve
10 Flow switch
DHW outlet
DCW inlet
DESCRIPTION
PH
Saturation factor(delta PH))
Total hardness
Conductivity
Sediments
Clorine
Hydrogen sulphide
Ammonia
Hydrogen carbonate
Hydrogen carbonate / sulphide
Sulphide
Nitrate
Nitrite
Sulphate
Manganese
Free iron
Free carbon dioxide
Primary return
Primary supply
LIMIT VALUES FOR COPPER SOL-
UNIT
DERED hEAT EXChANGER
pH
7-9 (including saturation factor)
pH
-0.2<0<+0.2
°Fr
15-30
µS/cm
10...500
mg/l
<30
mg/l
<0.5
mg/l
<0.05
mg/l
<2
mg/l
<300
mg/l
>1.0
mg/l
<1
mg/l
<100
mg/l
<0.1
mg/l
<100
mg/l
<0.1
mg/l
<0.2
mg/l
<20
16

Publicité

Table des Matières
loading

Table des Matières