Tabuchi Electric EneTelus EHW-S55P3B-PNUS Manuel D'installation page 16

Masquer les pouces Voir aussi pour EneTelus EHW-S55P3B-PNUS:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1
Attach the crimp terminal and insulating tube to the wire.
Insulating Tube
2
Connect the grounding line.
The inverter has a grounding terminal so as to securely ground
the equipment.
In order to prevent electric shock, be sure to connect the
ground securely.
Ground the breaker box through the inverter.
Class D grounding installation should be performed by a
licensed electrician in accordance with technical standards for
electrical equipment and internal wiring codes.
3
Connect the wires to the inverter terminal block and connectors.
Tightening torque: M5 screw ... 2 to 2.5 Nm
Signal wire strip gauge: 10 mm
*Tighten the M8 screw with a hex tool.
16
Crimp Terminal
Use the proper crimping tool for the screw size and
electric wire diameter of the terminal block.
Tightening torque: 8 to 13 Nm

Publicité

Table des Matières
loading

Produits Connexes pour Tabuchi Electric EneTelus EHW-S55P3B-PNUS

Table des Matières