+001111052201_00Ta.book Page 23 Friday, November 20, 2009 11:45 AM
High-Wall Type
2
Procedure
Each time you push
numbers in the control group change cyclically.
Select the indoor unit you want to change settings
for.
The fan of the selected unit runs and the louvers
start swinging. You can confirm the indoor unit for
which you want to change settings.
3
Procedure
Using temp. setup
CODE No. [
].
4
Procedure
Using timer time
DATA [
].
5
Procedure
Push
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat
2
from Procedure
.
• To change other settings of the selected indoor
unit, repeat from Procedure
Use
button to clear the settings.
To make settings after
repeat from Procedure
6
Procedure
When settings have been completed, push
button to determine the settings.
When
button is pushed, "SETTING" flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While "SETTING" is flashing, no operation of the
remote controller is accepted.)
23-EN
button, indoor unit
/
buttons, specify
/
buttons, select SET
3
.
button was pushed,
2
.
Change of lighting time of filter
sign
According to the installation condition, the lighting
time of the filter sign (Notification of filter cleaning)
can be changed.
Follow to the basic operation procedure
1
2
3
4
5
(
• For the CODE No. in Procedure
• For the [SET DATA] in Procedure
SET DATA of filter sign lighting time from the
following table.
Setup data
Filter sign lighting time
0000
0001
150H (Factory default)
0002
0003
0004
To secure better effect of heating
When it is difficult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can
be raised. Also use a circulator, etc. to circulate
heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
4
5
(
• For the CODE No. in Procedure
• For the SET DATA in Procedure
SET DATA of shift value of detection
temperature to be set up from the table below.
Setup data
Detection temp shift value
0000
0001
0002
0003
0004
0005
0006
– 23 –
Installation Manual
6
).
3
, specify [01].
4
, select the
None
2500H
5000H
10000H
6
).
3
, specify [06].
4
, select the
No shift
+ 1.8 °F (+1 °C)
+ 3.6 °F (+2 °C)
+ 5.4 °F (+3 °C)
(Factory default)
+ 7.2 °F (+4 °C)
+ 9 °F (+5 °C)
+ 10.8 °F (+6 °C)