LOVATO ELECTRIC GEX69-C Serie Mode D'emploi page 10

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

ƒ
DUAL POWER SUPPLY
SOLUTION 1
L1
Mains
N1
L2
Generator
N2
Voltage protection (e.g. LOVATO ELECTRIC PMV...)
Annex 4: electrical features table
Coperational torque
Rated operational voltage
Operating voltage range ‚
Operating voltage range acc. IEC 60947-6
Cable section of voltage supply
Cable section area Input Signals
Cable section area Auto-Lock mode Outputs
Inrush Current
Use current
Protective Fuseƒ
Operating angle
MU number of operations
Operation rate (0 - I - II - 0)
Operating temperature
Transportation and storage temperature
Weight
Based in our own tests
ƒ
Fuse reference F0,5AL250 V (Littelfuse)
Pos.
Direction
0
I
0
II
I
II
10
N
Cycles/hour
Pos.
Operating time
I
750 ms
0
750 ms
II
750 ms
0
750 ms
II
1.5 s
I
1.5 s
DUAL POWER SUPPLY
SOLUTION 2
L1
Mains
N1
L2
Generator
N2
L
Changeover siwtch
GE0160E/T4 - GE0400E/T4
Nm
20
V
230VAC/DC
ΔV
da 0.85V a 1.15V
ΔV
da 0.95V a 1.10V
2
mm
1.5 - 2.5
2
mm
0.5 - 1.5
2
mm
0.5 - 1.5
A
1.1
mA
45
A
1
- 70º / 0º / +70º (I - 0 - II)
Cycles
10000
120
-25ºC +55ºC
-40ºC +70ºC
kg
1.8
G
B
L
N
L
N
Changeover siwtch
GE0500E/T4 - GE0800E/T4
30
230VAC/DC
da 0.9V a 1.1V
da 0.95V a 1.10V
1.5 - 2.5
0.5 - 1.5
0.5 - 1.5
1.1
45
1
- 70º / 0º / +70º (I - 0 - II)
5000
60
-25ºC +55ºC
-40ºC +70ºC
1.8

Publicité

Table des Matières
loading

Produits Connexes pour LOVATO ELECTRIC GEX69-C Serie

Table des Matières