Examples of use:
Lamp on when everything is working regularly.
Lamp on when there is a malfunction.
I
NPUTS FOR DRY CONTACTS
If, at the time of connection to the grid, the inverter
must be able to manage the remote trip and signal
present signals envisaged in the CEI 0-21 regulation,
the inverter has two inputs for dry contacts. The pinout
of the connector is shown at the side of the board
itself.
If the installer uses the software to set to the inverter to
receive commands from the grid, the inputs take on
the following meaning:
IN1: "remote trip signal": interrupts feeding if the
contact is opened.
IN2: "communication signal": if the contact is opened,
the frequency thresholds are narrow.
If the interface supplied with the inverter does not have
the necessary inputs, it is possible to contact customer
service to adapt the product to requirements.