Commands' Menu; Settings' Menu - Aros SIRIO EVO 5000 Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

'COMMANDS' M
ENU
„AUTOTEST‟:
press
to access autotest mode (See Autotest paragraph for detailed information).
„UNLOCK‟:
if the inverter is locked (Lxx codes), press
'SETTINGS' M
ENU
„LANGUAGE‟:
and the display will read „LANGUAGE‟ on the first line and will show the currently set language on the second
Press
line. Press ↑ and ↓ to choose from: „Italiano‟, „Deutsch‟, „Español‟, „English‟, „Français‟.
Whatever language is set and whatever menu you are on, the language settings page can always be
accessed by pressing the ↑ and
English as the language.
„DATE & TIME‟:
press
and the display will show the current date (dd/mm/yy) on the first line and the current time on the second line
(hh:mm:ss S/L). This menu is a copy of the system clock: changing any field stops the progress of this copy (but not the
system clock).
The → arrow indicates the current field: the ↑ or ↓ keys can be used to edit the field and
next field. Keep ↑ or ↓ pressed to scroll quickly through the digits.
Clear the seconds by pressing ↑ or ↓ on the relative field.
Any change to/from daylight saving time can be made by pressing ↑ or ↓ on the S/L field.
on the last field of the screen (the S/L field) to automatically return to the „EXIT‟ menu if no change has been
Press
made. If a change has been made, the settings must be confirmed by pressing
In any case, you will now return to the „EXIT‟ menu.
The date can also be set from a PC using special software.
„ADDRESS‟:
press
and the display will show the current address.
The address on the RS485/422 bus can be set pressing ↑ and confirmed by pressing
quickly through the digits. Possible values include:
„AUTO‟: the inverter uses a mechanism of self assignment for the address.
From 1 to 255: fixed address on the bus.
NOTE: If using one of the following cards (inserted into the expansion slot):
XPV2RSA1B NetMan 102 Plus network card
XPV2RMC2A ModBus card
the address of the PV inverter must be set to AUTO (default value).
„NATION‟:
This screen is available for 12 hours subsequent to the initial setting of the nation of installation. During this period, the
installer can correct any error without requesting technical assistance.
and the display will read „NATION‟ on the first line and will show the currently set nation on the second line.
Press
Press ↑ or ↓ to change the set nation and
„PV CONFIGURATION‟
This screen is only available in inverters with more than one MPPT tracker for the first 12 hours of feeding after the initial
setting. It makes it possible to set the inverter for operation with two independent („independent‟) PV generators or with
inputs powered in parallel („parallel‟) by the same PV generator.
'LOW MAINS POWER'
This is the screen for the activation of the "Low Mains Power Power Limitation Function (VPD)". The inverter limits the
output power in order to avoid raising the mains voltage above the cut-off level set by the Country's regulations.
to force a recovery attempt.
buttons together. Holding them down for longer than 4 seconds sets
to confirm.
- 53 -
confirms and moves on to the
again, or cancelled by pressing ↑ or ↓.
. Keep ↑ or ↓ pressed to scroll