IN SERVICE

6.
6.1
The 2 local command buttons (figure A) are used to locally command the
shutters or blinds as follows:
• Pressing and long holding (> 0.5 s) the button, it moves the shutter or
blind UP (button 1) or DOWN (button 2) for the preset Movement Time.
• If the shutter or blind is moving, press and instantly release (<0.5 s)
either button to stop it.
• In blind mode, when the blind is at a standstill, each time the button is
pressed and instantly released (<0.5 s) will alter the inclination of the
laths.
6.2
When executing a scene, the shutter or blind will move to the previously
memorised transitional position.
When an alarm or override status is cancelled (receipt of an alarm or
override end command) the actuator will execute the last memorised
command and, if there are none, it will move to the position before the
alarm or override status occurred.
6.3
If the power to the bus decreases below 18 V dc for over 1.5 ms the
movement of the shutter or blind is interrupted
When the power is reinstated on the bus, the shutter or blind does not
move until it receives a new movement command.
6.4
This device requires no maintenance. Use a dry cloth for possible cleaning.

USING THE LOCAL COMMAND BUTTONS

TRANSITIONAL POSITIONS OF THE SHUTTER OR BLIND

BEHAVIOUR ON THE FAILURE AND REINSTATEMENT

OF THE BUS POWER SUPPLY

MAINTENANCE