Safety Guidelines

1.
Follow the installation instructions.
2.
Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3.
Note that the appliance is exclusively for use in the
applications detailed in these installation instructions
(see 2 Technical Data). Any other use will not be
considered to comply with requirements and would
invalidate the warranty.
4.
Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried
out by authorized persons.
5.
Immediately rectify any malfunctions which may
influence safety.
2

Technical Data

Media
Medium:
Connections/Sizes
Connection size:
Pressure values
Inlet pressure range:
Operating temperatures
Max. operating temperature
medium:
Specifications
Installation position:
Min. flow rate:
3

Options

For Options visit homecomfort.resideo.com/europe
4

Assembly

It is necessary during installation to comply with local
requirements, to follow codes of good practice and to follow
the installation instructions.
The installation location should be protected against frost and
be easily accessible
4.1 Installation Guidelines
Install shut-off valves
Install in horizontal pipework with spring bonnet
directed upwards
Ensure good access
– Pressure gauge can be read off easily
– Simplifies maintenance and inspection
Install a strainer upstream of the mechanical
disconnector
Cold drinking water
1
/
" - 2"
2
1.5 bar - 10 bar
40 °C
Horizontal with spring bonnet
upwards
1 l/min
GB
– To protect the mechanical disconnector from dirt
Mechanical disconnectors must not be fitted in any
areas or ducts where poisonous gases or vapours
may be present or where flooding can occur
If pressure shock is anticipated in the outlet side of the
disconnector, a pressure shock damper or expansion
vessel must be fitted on the system downstream of the
disconnector
In order to avoid flooding, it is recommended to
arrange a permanent, professionally dimensioned
wastewater connection
These armatures need to be maintained regularly
4.2 Assembly instructions
The opening pressure of the backflow preventer must
be correctly selected to match the system which is to
be protected. (see 4.3 Commissioning).
Flush connecting pipework thoroughly before
installation
Install the backflow preventer with good accessibility
and with flow in the correct direction
Install the backflow preventer only in horizontal
pipework and with the discharge tundish downwards
A clearance of A
backflow preventer for maintenance purposes
Rp
1/2" to 1"
A
100 mm
min
It is recommended that a Y-strainer  (e.g. FY 30) be
fitted upstream to protect the changeover valve and
backflow preventer against dirt.
Fit shut-off valves  and  either side of the
backflow preventer
Connect discharge pipe (DN 40 plastics pipe or R1"
threaded pipe) to discharge tundish 
The pressure gauge connection is fitted on the inlet
side of the backflow preventer.
CAUTION!
If there is a possibility, that at zero flow the water in
the downstream system may be heated, then a
safety valve must be fitted to allow for water
expansion and prevent the pressure rising above
the permitted level.
CAUTION!
If soldered union connectors are used the backflow
preventer must not be connected to the union
connectors during soldering.
4
must be provided above the
min
11/4" to 2"
150 mm
MU1H-1206GE23 R0420