Sensor Equipment; Sensor Resistance Values - evenes MMF 230.10.120 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

9 | SENSOR EQUIPMENT

The temperature sensor is preassembled on the fixed setpoint controller. In inflow
temperature control, assembly takes place on the inflow of the heating cycle, in
the in return flow temperature regulation it is assembled on the return flow of the boiler. The
recommended assembly location is approx. 0.5 m behind the heating pump. The heating tube
should be cleaned well and heat-conducting paste should be applied during the assembly of the
temperature sensor on the heating pipe. Alternatively, the temperature sensor can also be used
as an immersion sensor.

9.1 Sensor resistance values

Temperature
Resistance
[°C]
[W]
-20
922
-15
941
-10
961
-5
980
0
1000
5
1020
10
1039
15
1058
20
1078
25
1097
30
1117
Sensor PT1000
Temperature
Resistance
[°C]
[W]
35
1136
40
1155
45
1175
50
1194
55
1213
60
1232
65
1252
70
1271
75
1290
80
1309
85
1328
Temperature
Resistance
[°C]
[W]
90
1347
95
1366
100
1385
105
1404
110
1423
115
1442
120
1461
125
1480
130
1498
135
1415
140
1536
FIXED SETPOINT CONTROLLER MMF 230.10.120
INSTRUCTIONS
Temperature
Resistance
[°C]
[W]
145
1555
150
1573
155
1592
160
1611
165
1629
170
1648
175
1666
180
1685
185
1703
190
1722
195
1740
39

Publicité

Table des Matières
loading

Produits Connexes pour evenes MMF 230.10.120

Table des Matières