Safety Instructions Before And During Commissioning; Selecting Of The Heating Application - evenes MMF 230.10.120 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7 | SAFETY INSTRUCTIONS BEFORE AND DURING COMMISSIONING

7.1 Do not use if there is visible damage to the packaging or product.
Installing a damaged product could be life-threatening!
Ensure the correct opening direction of the mixer or valve when setting the fixed setpoint
controller. Incorrect rotation directions could lead to high or low temperatures in the
system. Minimum and maximum target temperatures are to be set correctly, incorrectly
selected threshold values lead to incorrect target temperature settings and consequently to unde-
sired operation which could cause damage to the system! Every system which is integrated into
the fixed setpoint controller must have independent system protection for temperatures which are
too low or too high. The fixed setpoint controller does not have a protection function in the
event of temperatures which are too low or too high.
7.2 Selecting and setting the applications, target temperature and mixer (valve)
direction of rotation.
The settings 'Application', 'Target temperature' or 'Direction of rotation' can be preset or
selected during commissioning.
7.2.1 Selecting the application
5s
basic display
Heating or cooling
After confirmation, the fixed setpoint controller continues operation with the altered setting!
34
FIXED SETPOINT CONTROLLER MMF 230.10.120
The setting is selected using the buttons
or
and confirmed with the
button.

Publicité

Table des Matières
loading

Produits Connexes pour evenes MMF 230.10.120

Table des Matières