Connection Diagram - ARO SHC5065 Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTALLATION

CONNECTION DIAGRAM

Caution! Voltage of heating elements 230V
Caution! In the event of any connection the safety
wire must be connected to the
1
For 230 V earthed one–phase
connection, bridges connect 1–2–3
terminals and 4–5 terminals, safety
.
wire to
2
For 400/230 V earthed two–phase
connection, bridges connect 2–3 ter-
minals and 4–5 terminals, the safety
.
wire to
3
For 400/230V earthed three–phase
connection, bridges connect 4–5 ter-
minals, phases in succession 1,2 and
3, earth to 4–5, the safety wire to
L1, L2, L3 =Live, N=Earth terminal, PE= Safety wire terminal
PE terminal
.
17
3
4
5
2
N
1
L1
PE
3
4
5
2
N
L2
1
L1
PE
3
4
L3
5
2
N
L2
1
L1
PE
Recommended
type
of connection
lead
H05VV-F3G4
3X 4 mm
2
H05VV-F4G2,5
4X 2,5 mm
2
H05VV-F5G2,5
5X 2,5 mm
2

Publicité

Chapitres

Table des Matières
loading

Produits Connexes pour ARO SHC5065

Table des Matières