Installation, Maintenance and Operation Manual
Electric Actuator
Setting Cams for Alignment
E
(Continued)
N
1B. If valve travels too far past open;
G
Manually rotate shaft CW past the
L
open position. Follow instructions in
I
1A for "Setting Open Position".
S
SETTING CLOSE POSITION
H
2A.If valve did not close completely;
Turn power off. Remove cover.
Loosen set screw in bottom cam &
rotate counterclockwise. Manually
rotate shaft clockwise to desired
close position. Slowly rotate cam
clockwise until switch lever opens.
You should hear a light click.
(To check using a multi-meter:
Set multi-meter to "Resistance" or
"Continuity" mode. Connect leads to
terminals 3 & 5, rotate cam clockwise
until switch lever opens & continuity
is achieved.) Tighten set screw to set
close position.
Wiring Diagrams
ELECTRIC ACTUATOR
WIRING DIAGRAM
120 VAC / 230 VAC 1 Phase
50 - 60 Hz
ELECTRIC ACTUATOR
WIRING DIAGRAM
12 - 24 VDC & 24 VAC 1 Phase
NOTE: Field wiring is shown for
reference only: not supplied with
the actuator.
2B. If valve closed too far;
Manually rotate shaft counter-
clockwise past close position. Follow
instructions in 2A for "Setting Close
Position".
Restore electric power to actuator and
operate the unit several times and
recheck positions. If still out of
alignment, repeat setting cams for
alignment. Replace cover.
Maintenance
Under normal operation, electric
actuators require no formal
maintenance program.
SW1 - Close
SW2 - Open
SW2
SW1
AC Voltage
SW1 - Close
SW2 - Open
SW2
SW1
AC/DC Voltage
Low Voltage
DynaQuip Controls 800-545-3636 www.dynaquip.com
2
www.comoso.com
Regularly scheduled inspections should
be performed to check for:
• Actuator-to-valve misalignment
• Damaged housing or mounting
hardware
• Worn, loose or shifted parts due to
shock, vibration, etc.
STORAGE
Store in a clean, dry environment and
protect from severe temperature
changes and vibration.
NOTE: After Installation it is the
customers responsibility to be certain
that all set screws, terminal screws,
housing bolts and mounting bolts
are tight, and limit switches,
potentiometers and position
transmitters are calibrated to the
individual settings required for their
specific application.
POWER TO TERMINALS;
1 & 2 TO OPEN
1 & 3 TO CLOSE
TERMINALS 4 & 5 FOR
FIELD REMOTE SIGNALS
+ POWER TO 6 FOR
HEATER OPERATION
SPDT SWITCH SHOWN
FOR ILLUSTRATION ONLY
Field Wiring
POWER TO TERMINALS;
1 & 2 TO OPEN
1 & 3 TO CLOSE
TERMINALS 4 & 5 FOR
FIELD REMOTE SIGNALS
+ POWER TO 6 FOR
HEATER OPERATION
SPDT SWITCH SHOWN
FOR ILLUSTRATION ONLY
Field Wiring