Installation of the Pump

Grinder pumps must be installed in a tank that is vented in accordance with local plumbing codes.
Installation should be at a sufficient depth to ensure that all plumbing is below the frost line. If this is not feasible,
remove the check valve and size the basin and/or adjust pump differential to accommodate the additional
backflow volume. Consult the factory for details on how this should be done.
6.x
Electrical Service & Operation
Risk of electric shock. Always disconnect the pump from the power source before handling or making
adjustments.
The electrical connections and wiring for a pump installation should only be made by qualified personnel.
This pump is supplied with a grounding conductor or a grounding type attachment plug. To reduce the risk of
electric shock, be certain that the grounding conductor is connected only to a properly grounded control panel
or, if equipped with a grounding type plug that it is connected to a properly grounded, grounding type
receptacle.
DO NOT bypass grounding wires or remove ground prongs from attachment plugs.
DO NOT remove cord and strain relief and DO NOT connect conduit to pump.
DO NOT use an extension cord.
This pump requires separate, properly fused and grounded branch circuit. Make sure the power source is
properly sized for the voltage and amperage requirements of the motor, as noted on the pump nameplate.
The electrical outlet or panel shall be within the length limitations of the pump power cord, and at least 4 feet
above floor level to minimize possible hazards from flood conditions.
The installation must be in accordance with the National Electric Code and all applicable local codes and
ordinances.
THIS PUMP IS NOT TO BE INSTALLED IN LOCATIONS CLASSIFIED AS HAZARDOUS IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE,ANSI/NFPA 70.
When the risk of property damage from high water levels exists, an independent high water
alarm should be installed. A duplex pumping system is recommended for critical installations.