8.5 Interface de paramètres de la régulation du parc
Mot de
Nom de variable
données
72.0
P_Mode_IntAbs
76.0
P_Mode_IntQC
78.0
P_Mode_ManRel
82.0
P_Mode_ManAbs
86.0
P_Mode_ManQC
88.0
P_Mode_Source
90.0
P_Ramp_LockUp
90.1
P_Ramp_LockDn
92.0
P_Ramp_TimeUp
96.0
P_Ramp_TimeDn
100.0
P_Ramp_RampUp
104.0
P_Ramp_RampDn
108.0
P_Delta_Enable
110.0
P_Delta_F_High
114.0
P_Delta_F_Norm
118.0
P_Delta_F_Min
122.0
P_Delta_F_Max
126.0
P_Delta_F_Hys
130.0
P_Delta_Grad_dP
134.0
P_Cont_Gain
138.0
P_Cont_TN
142.0
P_Cont_LLM
146.0
P_Cont_HLM
150.0
Q_Mode_Bypass
152.0
Q_Mode_CosPhi
156.0
Q_Mode_CosPhiQC
158.0
Q_Mode_Q
162.0
Q_Mode_Q_QC
164.0
Q_Mode_Source
54
Type de
Désignation
données
BYTE
P mode internal absolute
setpoint active power [kW]
REAL
P mode Quality Code internal
setpoint P
REAL
P mode manual relative setpoint
active power [%]
BYTE
P mode manual absolute
setpoint active power [kW]
BYTE
P mode Quality Code manual
setpoint P
INT
P mode source (0: Plant;
1: ExtR; 2: ExtA; 3: IntR; 4: IntA;
5: ManR; 6: anA)
BOOLE
P ramp locked ramp up
BOOLE
P ramp locked ramp down
REAL
P ramp time up to get value [s]
REAL
P ramp time down to get value
[s]
REAL
P ramp ramp up [%]
REAL
P ramp ramp down [%]
INT
P Delta enable
REAL
P Delta high Frequency [Hz]
REAL
P Delta norm frequency [Hz]
REAL
P Delta minimum frequency [Hz]
REAL
P Delta maximum frequency [Hz] 51.5
REAL
P Delta Hysteresis limit
frequency back to normal [Hz]
REAL
P Delta Gradient of frequency
reduction per Hz in %
REAL
P Controller Propotional Gain
TIME
P Controller reset time
REAL
P Controller low limit
REAL
P Controller high limit
BOOL
Q mode activate bypass
REAL
Q mode Power Factor cosPhi
BYTE
Q mode Quality Code Power
Factor cosPhi
REAL
Q mode reactive power Q
BYTE
Q mode Quality Code reactive
power Q
INT
Q mode source (0: cosP = 1;
1: Cos = x; 2: CosP (t);
3: CosP (P); 4: Q = x; 5: Q(U);
6: Q_Cont)
Valeur
Accès
par
Lecture/
défaut
écriture
0.0
r / w
16#80
r / w
0.0
r / w
0.0
r / w
16#80
r / w
1
r / w
(ExtR = E
VU)
False
r / w
False
r / w
30.0
r / w
30.0
r / w
20.0
r / w
20.0
r / w
0
r / w
50.2
r / w
50.0
r / w
47.5
r / w
r / w
50.05
r / w
40.00
r / w
0.2
r / w
T#4s
r / w
0.0
r / w
100.0
r / w
False
r / w
1.0
r / w
16#80
r / w
0.0
r / w
16#80
r / w
0
r / w
Instructions de service, 01/2013, A5E03642519A/003
Champ
obligatoire
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
PVS ControlBox 300