Simplified Installation (Return/Return Method); Installation Notes - Airia LIFEBREATH PURE PERFORMANCE ERV Serie Guide D'installation

Table des Matières

Publicité

Simplified Installation (Return/Return Method)

Installation Notes

The ERV must be balanced.
Unit should be balanced on high speed with the furnace
blower on.
It is mandatory that the furnace blower run continuously
or ERV operation be interlocked with the furnace blower.
The duct configuration may change depending on the
ERV model.
A backdraft damper is recommended in the exhaust air
duct to prevent outdoor air from entering the unit.
The airflow must be confirmed on site using the
balancing procedures found in this guide.
Spring-Loaded Backdraft Damper (Recommended)
There is a location for an optional Backdraft Damper with the leaf hinge vertical. The damper is
installed on the "Stale Air to Outside Collar"
RETURN
AIR
Stale Air
to Outside
Fresh Air
from Outside
Attention/Warning
Check local codes/authority having jurisdiction for acceptance.
Applications such as greenhouses, atriums, swimming pools, saunas, etc. have unique ventilation requirements
which should be addressed with an isolated ventilation system.
Weatherhood arrangement is for drawing purposes only. Check local codes/authority having jurisdiction for
acceptance.
Backdraft dampers are recommended for the stale air to outside air duct. This damper prevents outdoor air from
entering the ERV during the operation of the furnace/air handler while the ERV is in standby, off, or recirculating.
DIRECT CONNECTION of both the ERV SUPPLY AIR STREAM and
EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN
Dampers for balancing
air flows, if not in collars of unit
Install backdraft damper
to ERV collar with leaf
hinge vertical
Forced Air
Furnace
4

Publicité

Table des Matières
loading

Table des Matières