Press On/Off button within 10 sec-
onds, and the test operation starts.
Monitor the operation of the indoor unit
for a minimum of 10 minutes. During
test operation, the indoor unit will
continue to cool regardless of the
temperature setpoint and room
temperature.
Note) In the case of above-men-
tioned procedures
7-4
in reverse order, test
operation can start as well.
7-5
Press
Menu/OK button in the basic
screen. Main menu is displayed.
7-6
In the case of a model having airfl ow
direction function, select
Airfl ow Direction
and check that airfl ow direction is
actuated according to the setting.
For operation of airfl ow direction
setting, see the operation manual.
7-7
After the operation of airfl ow direction
is confi rmed, press Menu/OK button.
Basic screen returns.
7-8
Press and hold
Cancel button for
4 seconds or longer in the basic
screen.
Service settings menu is displayed.
7-9
Select
Test Operation
settings menu, and press Menu/OK
button. Basic screen returns and
normal operation is conducted.
Note) The test operation will automat-
ically fi nish in 30 minutes.
7-10
Check the functions according to the
operation manual.
7-11
When the decorative panel is not
installed, shut off the power supply
after the test operation fi nishes.
If construction activities are planned within
the space following the test operation
procedure, recommend to the customer
that the indoor unit is not operated to
prevent contamination from paints, drywall
dust and other airborne materials.
16
7-3
and
in the main menu
in the service
7-
4
7-
5
Cool
Set temperature
28
Test Operation
<Main menu screen>
7-
6
Main Menu
Airflow Direction
Individual Airflow Direction
Ventilation
Schedule
Off Timer
Celsius / Fahrenheit
Setting
7-
7
Airflow Direction
Swing
Setting
7-
8
Cool
Set temperature
28
Test Operation
7-
9
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Setting
<Basic screen>
Press On/Off button
°C
(within 10 seconds).
Press Menu/OK button.
1/3
Press Menu/OK button.
Change the airfl ow
direction by using
(Up/Down) button.
Press Menu/OK button.
°C
Press and hold Cancel
button for 4 seconds or
longer while the backlight
is on.
1/3
Press Menu/OK button.
English