Hydraulic Diagrams; Solar Thermal System - Program 0 - 2 - Technische Alternative ESR 31 Mode D'emploi

Masquer les pouces Voir aussi pour ESR 31:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Hydraulic diagrams

Solar thermal system - program 0
S1
A
The solar pump A runs when S1 has a temperature of diff higher than S2 and S2 has not
exceeded the threshold max.
In addition, the pump's protective function takes effect: During a standstill, steam can oc-
cur in the system. When automatically switched on again, the pump does not have the re-
quired pressure in the steam phase to lift the fluid level to the collector's supply line (highest
point in the system). This represents a considerable load on the pump. The collector's excess
temperature shut-down function can be used to block the pump whenever a certain tempera-
ture has been reached at the collector's sensor until a second threshold, which can also be
set, is fallen short of again. The settings ex works are 130°C for the blockage and 110°C for
the release. The settings can be changed in the menu MEN, sub-menu SYS PF/CET (collec-
tor excess temperature).
Program 1:
With this program, the solar thermal system has an additional storage limit max2 via sen-
sor S3. There is no guarantee that the actual storage temperature will lead to a cut-off in
time, especially if the reference sensor S2 is installed at the return outlet for the heat ex-
changer.
Program 2:
As program 0, however with additional 10 V burner requirement via S3 at control output.
Additional required settings:
max2 ... COP off (0V)
min2 ... COP on (10V) S3 (ex works = 40°C)
A = S1 > (S2 + diff) & S2 < max
Control output COP:
Subsequently, an auxiliary relay can be connected to the control output HIREL-STAG, which
forwards the burner requirement in potential-free format. The active control output is indicat-
ed by the flashing burner symbol in the display.
S3 for program 1 and 2
S3
diff
S2
max
S3 (ex works = 65°C)
10 V = S3 < min2 (burner on)
0 V = S3 > max2 (burner off)
= factory settings
Required settings :
S1
max ... limit TK S2
max2 ... see program 1 or 2
min2 ... see program 2
... coll. S1 – TK S2
diff
S2
English
7

Publicité

Table des Matières
loading

Table des Matières