Electrical Connection - Technische Alternative ESR 31 Mode D'emploi

Masquer les pouces Voir aussi pour ESR 31:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Electrical connection

Caution: Only a trained electrician may provide the electrical connection in compliance
with local guidelines. The sensor lines must not be laid in the same cable channel as the
supply voltage. The maximum load of the output is 3A = 700W! If filter pumps are directly
connected, their rating plate must be minded. The appropriate strip terminal must be used for
all protective conductors.
Note: The system has to be grounded properly and furnished with surge arresters to pro-
tect it from damage due to lightening. Sensor failures due to storms and static electricity are
usually the result of faulty construction.
The sensor masses
Control output (0 – 10V / PWM)
This output is intended for the speed control of the latest generation electronic pumps
(PWM) or for controlling the burner performance (0 - 10V). It can be operated via respective
menu functions parallel to the output.
Data link (DL)
The bi-directional data link was developed for the ESR/UVR series and is only compatible
with products of the Technische Alternative company. Any cable with a cross section of 0.75
mm² can be used for the data link (e.g. twin-strand) having a max. length of 30 m. For longer
cables, we recommend the use of shielded cable.
Interface to PC: The data is cached via the data converter D-LOGG, Bootloader BL-
NET or C.M.I. interface and transferred to the PC on request. BL-NET and C.M.I. require a
separate 12V power unit for power supply.
External sensors: Reading the values of external sensors with DL connector
are internally connected and can be exchanged as needed.
English
19

Publicité

Table des Matières
loading

Table des Matières