1. Functional Description

This setpoint generator is an easy-to-use micro-
processor-controlled device outputting current and
voltage values.
Current:
0 ... 24 mA
Voltage:
0 ... 12 V DC
Either the current or the voltage output can be
used.

1.1 The SEtP Operating Mode

In this mode, the device is operated in manual
direct input operation after programming: the
value is input here directly in volts or mA. If no
other key is depressed within 3 seconds, the value
input will be considered as the new setpoint and
will be output by the device. During operation, the
display alternates between the output setpoint and
the message SEtP.

1.2 The MAn Operating Mode

In this mode, the device is operated in manual
ramp operation after programming: this operation
is defined by means of 2 freely selectable
current or voltage values and by the increment.
During operation, press the right key to increase
the setpoint by the increment programmed, press
the left key to reduce the setpoint accordingly. In
addition, the device offers the possibility to apply
a scale factor to the setpoint output. It is possible
to display e.g. 10 (kg) while 2 V are output. During
operation, the display alternates between the out-
put setpoint and the message MAn.

1.3 The Auto Operating Mode

In this mode, the device is operated in automatic
ramp operation after programming. The automatic
ramp function is defined by means of a maximum
of 20 current or voltage values which are output
in a synchronized way. The ramp function can be
programmed either as a limited or as an endless
loop. Cycle time can be programmed in the range
of 0.1 s ... 999.9 s or 0.1 min ... . 999.9 min. The
1st cycle of the automatic ramp function is started
with the right key.
EN - Page 2
Three operating modes can be programmed:
– Manual direct input operation
– Manual ramp operation
– Automatic ramp operation
Data backup for power failure
The programmed data remains saved even in case
of a power breakdown.
The ramp function can be ended with the left key.
The automatic ramp function can be stopped by
activating the Hold input.
After deactivating the input, it resumes operation
at the point where it stopped. During operation, the
display alternates between the output setpoint and
the message Auto.