Electric Actuator
DC Voltage, 12 – 24 Vdc
ADJUST OPEN POSITION
Unit not in full open position.
a) Apply power to terminals 1 & 2 to move the open cam knob clockwise toward open position. Do not remove
power.
b) With a 3/8 wrench, move open cam knob counter-clockwise slightly and release, to jog motor, until motor
moves the drive shaft to the desired open position. If necessary, repeat jogging movement until desired open
position is attained. Use the flats on the drive shaft as a guide for position.
Unit past full open position.
a) Apply power to terminals 1 & 3 to move actuator drive shaft to the closed position. At this time turn open
cam knob to align the notch at the base of the knob, with the ground screw.
b) Reapply power to terminals 1 & 2.
c) With a 3/8 wrench, move open cam knob counter-clockwise slightly and release, to jog motor, until motor
moves the shaft to the desired open position. If necessary, repeat jogging movement until desired open position
is attained.