Ventilation; Auxiliary Pump; Wiring - NOVARDEN NSH35s Manuel D'installation Et D'utilisation

Pompe à chaleur mini pour piscine
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

EN
Heat pump installation

Ventilation

Do not obstruct ventilation. Incoming and outgoing air must be able
to circulate freely.
Keep a space of at least 50cm around the appliance otherwise the
machine's efficiency could be reduced or even prevented.

Auxiliary pump

The appliance needs to use an auxiliary pump (provided by the
manufacturer). To ensure the recommended pump flow rate, refer
to the technical parameters. Discharge head ≥10m.

Wiring

Make sure the correct voltage is used to operate the appliance. Also
check that the appliance is correctly grounded. The wiring must be
undertaken by a professional technician and be in accordance with
the wiring diagram provided.
You must install a ground fault circuit interrupter in compliance
with the electrical installation legislation (leakage detecting current
≤ 30mA).
The power cable and interface cable must be installed in accordance
with current regulations and the cables must be connected
separately.
10

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Nsh55s

Table des Matières