3-7. Operating Mode/Status Description

Operating mode/status
Description
AC mode
LCD display
Description
CVCF mode
LCD display
Description
Battery mode
LCD display
Bypass mode
Description
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
52
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 11 16 AA XX 201 07
Setting
Parameter 3:
Calibrate the displayed backup time by adjusting this multiplier
factor. The calculation is as below:
Displayed backup time=Original calculated backup time x
Multiplier factor
The default value of the multiplier factor is 1.0, and the range is
from 0.5 to 2.
When the input voltage is within the acceptable range, the UPS will
provide pure and stable AC power to output. The UPS will also charge
the battery in AC mode.
When the input frequency is within 46 and 64Hz, the UPS can be set at
a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge
the batteries in this mode.
When the input voltage is beyond the acceptable range or during a
power failure, the UPS will backup power from the batteries and the
alarm will beep every 4 seconds.
When the input voltage is within the acceptable range and the bypass is
enabled, turn off the UPS and it will enter the Bypass mode. The alarm
beeps every two minutes.